On Friday, August 14, 1998 1:14 PM, Geoff Savage [SMTP:[email protected]] wrote:
> Hi,
>
> Is it possible to increase the scan rate to greater than 10 Hz (.1 second)?
>
Higher scan rates can be obtained by configuring the record's SCAN field to
"I/O Interrupt" or "Event". The former causes the record to be processed
when device support calls scanIoRequest(), and the latter causes the record
to be scanned when some application program calls post_event().