**** Has anybody else experienced these problems? ****
When we are operating sliders to write process variables through the CA
gateway, every now and then on releasing the sliders the gateway writes
huge (and I mean r e a l l y huge positive or negative) numbers to
the IOC, which set the PV to the upper or lower end of the allowed range.
This never happens if you don't use the gateway.
We observed this behaviour both with dm and with edm (running on Solaris
or Linux Redhat 9).
The gateway is running on a Linux (Redhat 9) box. Several gateway
releases up to Beta18 (built against EPICS R3.14.6) exhibit this behaviour.
We lost a couple of devices, where a user hadn't specified a proper DRVH
for the setpoint.
We have taken the gateway out of operation until this is resolved.
- rolf -
--
+-------------------------------------------------+
| Rolf Keitel, TRIUMF Tel: (604) 222-7453 |
| Group Leader ISAC Controls Fax: (604) 222-7307 |
| and Electronics Development |
| Vancouver, B.C., Canada |
+-------------------------------------------------+
- Replies:
- Re: dm and edm problems with CA gateway Ralph Lange
- RE: dm and edm problems with CA gateway Jeff Hill
- Navigate by Date:
- Prev:
Re: Maximum of a waveform record Andrew Johnson
- Next:
Re: dm and edm problems with CA gateway Kenneth Evans, Jr.
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: CA Wish List, and Essential Preexisting Features List Liyu, Andrei
- Next:
Re: dm and edm problems with CA gateway Ralph Lange
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024