Hi Ge,
Three things I'd suggest (based on my experience with 100 series hardware):
1) make sure your EVG is properly "seated" in the crate. Even if LEDs are
on, I've found that board can be incorrectly seated. This happened with
64x VME crates.
2) ensure the top rotary dial is set to '2' and the lower rotary dial is
set to '0'
3) change your card number from '4' to '0' if you only have one EVG
Step (3) may not be necessary to get it working.
You need to get a '0' return code from EgConfigure before you can get
any further.
The same suggestions apply to EVR (rotaries at '1' and '8', change
card to '0'). For EVR only, check that jumpers are set to '5' as
is documented on the board itself.
Dayle Kotturi
LINAC Coherent Light Source
Stanford Linear Accelerator Center
On Tue, 20 Sep 2005, Lei Ge wrote:
Hello,
I'm testing the event generator EVG200, but my IOC failed to probing the
event-generator board. Could somebody give me some suggestions? Thank you
very much.
---------------------------------------------------------
EgConfigure(4,0x2000)
value = -1 = 0xffffffff = prsrv_cast_client + 0xff0f7b3f
ErConfigure(6,0x1800,164,5)
value = -1 = 0xffffffff = prsrv_cast_client + 0xff0f7b3f
cd "/home21/home/leige/epicsApp/dbd"
value = 0 = 0x0
dbLoadDatabase("baseApp.dbd")
devApsEg: Failure probing for event generator... Card disabled
devApsEr: Failure probing for event receiver... Card disabled
value = 0 = 0x0
dbLoadDatabase("evgevr.dbd")
value = 0 = 0x0
----------------------------------------------------------------
Best wishes,
Ge