1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Genesys Power Suppy LAN driver |
From: | Dirk Zimoch <[email protected]> |
To: | "Tagle, Jerico" <[email protected]> |
Cc: | [email protected] |
Date: | Tue, 14 Apr 2009 10:34:26 +0200 |
Hello Jerico,It should be sufficient to replace the drvAsynSerialPortConfigure like in your startup script with a drvAsynIPPortConfigure line.
If the device uses the vxi11 protocol ("GPIB over ethernet") use a vxi11Configure line instead.
Dirk Tagle, Jerico wrote:
Greetings All, My name is Jerico Tagle and I work at SLAC National Accelerator Labaratories in Menlo Park, CA. We have successfully communicated with the Genesys 300-17 via RS232 on EPICS (Thanks to Mr Dennis Armstrong @ PSI) and would like to communicate with it via LAN. If you have existing drivers for the Genesys power supplies via LAN, can you please send me a copy? My forte is Power Electronics and I am attempting to learn EPICS to control our power supplies for the future. Thnks For Your Time! Jerico Tagle
-- Dr. Dirk Zimoch Paul Scherrer Institut, WBGB/006 5232 Villigen PSI, Switzerland Phone +41 56 310 5182