1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: CA link behavior |
From: | Emmanuel Mayssat <[email protected]> |
Cc: | [email protected] |
Date: | Fri, 13 Nov 2009 14:09:42 -0800 |
Another reason you may see this is because of autosave or the like. -- E
I have a passive stringout record in IOC A whose OUTLINK references an mbbo record in IOC B. When I reboot IOC B the value in the stringout record is written to the mbbo record even though the stringout record has not been processed. A bit more background. The stringout record will be processed by a calc record when a temperature becomes too high. The mbbo record controls the power to a front end board. So the value being written is to power off the front end board whenever the IOC B is rebooted.