Andrew -
Did you know the AO record has built in ramping and built in drive limits and built in operating range and a convenient VAL field for the MEDM interface?
Ned
On Aug 17, 2010, at 9:17 PM, Tim Mooney wrote:
> Hi Andrew,
> Replies embedded:
>
> On 8/17/2010 6:13 PM, Andrew Wagner wrote:
>> Hey again,
>>
>> I'm pretty close to having my magnet ramp code implemented but I need to know how to have a record access a user defined input during run time. For instance I want to turn a dial in MEDM to set the ramp point of the magnet. So far I've implemented a database as follows:
>>
>> #Calc Coil Current
>>
>> record(calc, "Current:Coil") {
>> field(DESC, "Coil Current")
>> field(SCAN, "Passive")
>> field(MDEL, ".1")
>> field(ADEL, ".1")
>> field(CALC, "LA + A*1/1200")
>>
> This expression won't be understood. You could say this:
> field(INPB,"Current:Coil.A")
> field(CALC,"B+A*1/1200")
>> field(INPA, "$(MUX):VOLT:Chan204.VAL PP MS")
>> field(PINI, "NO")
>> field(EGU, "A")
>> field(SDIS, "0")
>> }
>>
>> #Calc output and write to AG3631 Voltage programmer
>>
>> record(calcout, "Voltage:Output") {
>> field(DESC, "Output Voltage")
>> field(SCAN, "1 second")
>> field(CALC, "Voltage:Output.VAL + (B - A)*.5/1")
>>
> This calc expression won't be understood. You could say this:
> field(INPC,"Voltage:Output.VAL")
> field(CALC,"C + (B - A)*.5/1")
>> field(INPA, "Current:Coil.VAL PP MS")
>> field(INPB, "Runtime Input") # How do I link to user input?
>>
> You can either use a separate record, and point INPB at that record's VAL field, or
> you can have the user write directly to Voltage:Output.B. The first solution is better
> if you want to enforce limits or attach engineering units, precision, a description, etc.
>
> The two choices can't in this case make any difference in the algorithm, because
> Voltage:Output is periodically scanned. If it were "Passive", writing directly to B
> from a CA client would process the calcout record whenever the user wrote, but
> using the INPB link to read from a separate record would not have this effect.
>
>> field(OOPT, "On Change")
>> field(DOPT, "CALC")
>> field(DTYP, "AG3631")
>> field(OUT, "#L$(L) $(A) @0")
>> field(PINI, "NO")
>> field(EGU, "V")
>> field(SDIS, "0")
>>
>> }
>>
>> How do I set the INPB to link to a runtime input? I've seen an example where a "dummy" AI record is linked, but I'm not sure if there is a better way. I would also like to put some protection logic in place. For instance, I would like to calculate a V_min and V_max (functions of Current:Coil) that Voltage:Output must be between in order for the OUT link to be processed. Are there any examples of how to implement this? The documentation doesn't really have any. Thanks again for your help.
>>
>>
> You could use a separate output record, and have two calcout record's write to its DRVH and DRVL
> fields. This would clip the output at those values.
>>
>>
>>
>>
>>
>>
>>
>>
>
> --
> Tim Mooney ([email protected]) (630)252-5417
> Software Services Group, Advanced Photon Source, Argonne National Lab.
>
- References:
- Runtime Input Question Andrew Wagner
- Re: Runtime Input Question Tim Mooney
- Navigate by Date:
- Prev:
sCalcout Pierrick Hanlet
- Next:
Re: sCalcout Kurt Goetze
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Runtime Input Question Tim Mooney
- Next:
sCalcout Pierrick Hanlet
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024