1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: pyepics callback function problem
From: Janko Kolar <[email protected]>
To: Matt Newville <[email protected]>
Cc: [email protected]
Date: Fri, 07 Jan 2011 13:58:28 +0100
Hello

Your suggestion solved the problem.

Thank you for your quick response.

                               Janko
Hi Janko,

I hope this is a right place to ask a question about pyepics.

I think it is.

I wrote a simple program to monitor their value:

import sys
import time
from epics import PV

def callback_function(pvname=None, value=None, char_value=None,
type=None,units=None, enum_strs=None, **kw):
    print "------Printout from callback ------"
    fmt = ' pvname \t = %s \n value \t\t = %s \n\
char_value \t = %s \n type \t\t = %s \n\
units \t\t = %s \n enum_strs \t = %s \n'
    print fmt % (pvname, value, char_value, type, units, enum_strs)
    print "----------------------------------\n"

pll = PV('LUCA:ENV:ENV_SC_PLL_MONITOR')

vent = PV('LUCA:ENV:ENV_FRONT_VENT_ACT_MONITOR')

pll.add_callback(callback_function)
pll.run_callbacks()

vent.add_callback(callback_function)
vent.run_callbacks()

while True:
    time.sleep(0.001)


Sorry for the trouble.

The issue is that not all of the "extra control fields" (including the
names of the enumeration states, units, and precision) have been
determined when you do PV.run_callbacks().  That is only the "native
form" of the PV

The easiest fix is to explicitly make the control fields be looked up,
either with PV.get_ctrlvars() or PV.get(as_string=True) which also
makes sure that the "char_value" is well formed.  That is, I think you
want

   pll.add_callback(callback_function)
   pll.get(as_string=True)
   pll.run_callbacks()

   vent.add_callback(callback_function)
   vent.get(as_string=True)
   vent.run_callbacks()

   while True:
       time.sleep(0.001)

Perhaps an option should be added to PV.add_callback() to make sure
the control fields are initialized.  Either that, or this should be
better documented.

--Matt Newville <newville at cars.uchicago.edu> 630-252-0431



References:
pyepics callback function problem Janko Kolar
Re: pyepics callback function problem Matt Newville

Navigate by Date:
Prev: Re: GPIB to ethernet converter Eric Williams
Next: Re: MOXA terminal server Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: pyepics callback function problem Matt Newville
Next: Test, please ignore Benjamin Franksen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  <20112012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024