1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 <2012> 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 <2012> 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: carrier card Hy8002 error |
From: | [email protected] |
To: | huili <[email protected]> |
Cc: | [email protected] |
Date: | Mon, 26 Mar 2012 23:24:25 +0100 |
Hi Huili,From the printout it looks like you might have loaded two IOCs at the same time. If you can check the generic start-up st.cmd file (maybe under the localhome folder for example) , you might find two entries there. If there are more than one, commenting out one will solve the problem.
Best regards, Jim Hytec Electronics Ltd Quoting huili <[email protected]>:
My ioc download message about Hy8002 as this: IPAC3 = ipacAddHy8002("9,2") filename="../../../src/libCom/osi/devLib.c" line number=373 Specified device address overlaps another device VME A16 0X00004C00 - OX00004C9F Requested by drvHy8002filename="../../../src/libCom/osi/devLib.c" line number=399 This device already owns the address range VME A16 0X00004C00 - 0X00004C9F Owned by drvHy8002ipacAddCarrier: Hytec VICB8002 driver returned an error. IPAC3 = 0x1e3ee420: value = 39321603 = 0x2580003 I don't know how to so ,Please give me a soluton! Best wishes!
---------------------------------------------------------------- This message was sent using IMP, the Internet Messaging Program.