1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 <2013> 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 <2013> 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | MAXV card with firmware version 1.42 |
From: | <[email protected]> |
To: | <[email protected]> |
Date: | Mon, 25 Mar 2013 09:27:36 +0000 |
All, Comment from Prodex OMS: I can confirm that in your FW1.42 the #WS does not work in single axis mode. It still works in AA/AM mode. This was unintentional and we will provide a fix shortly. If you are using the latest release of the motor support module, you may have problems with the #WS command that is used to detect watchdog timeouts in the OMS MAXv driver. Regards, Austen Rose Senior Software Engineer +44 (0)1235 77(8495) Diamond Light Source Ltd Diamond House Harwell Science and Innovation Campus Didcot Oxfordshire OX11 0DE United Kingdom
-- This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail. |