Hi
If we take the data to be 2's complement, then, by referring to
modbusDoc.html, this would be modbusDataType value 4.
We use modbus function 4 in drvModbusAsynConfigure and then create a
record:
record(ai, temp:bar) {
field(DESC, "temp probe input")
field(SCAN, "Passive")
field(DTYP, "asynInt32")
field(INP, "@asynMask(TempProbeRead, 0, 16,100) INT16 ")
field(LINR,"LINEAR")
}
but when starting the IOC, we get error output:
temp:bar devAsynInt32::initCommon findInterface asynInt32Type invalid
INST_IO Must be asyn(<port> <addr> <timeout>)userParams
asynMask syntax is rejected, and only with
asyn(TempProbeRead, 0, 100) INT16)
do we get no _startup_ erors.
asyn version 4-17
modbus 2-2
base 3.14.12.3
stefani banerian
On 05/13/2013 03:53 PM, Mark Rivers wrote:
> Hi Stefani,
>
> I looked a little more closely at the Omega manual:
>
> http://www.omega.com/manuals/manualpdf/M3397.pdf
>
> On page 40 they give an example of setting Alarm2 to -100.0. This is done in 2 steps:
>
> - Set the decimal point to position 2 (FFF.F).
> - Send the value -1000 in 2's complement format.
>
> This shows that the meter does use 2's complement for signed integers.
>
> Mark
>
>
> -----Original Message-----
> From: Mark Rivers
> Sent: Monday, May 13, 2013 5:12 PM
> To: '[email protected]'; EPICS Tech Talk
> Subject: RE: Modbus TCP and Omega
>
> Hi Stefani,
>
> Are you using my EPICS Modbus module?
>
> When you say "it sends back its data as hex", how are you getting the 00 e6 value? Using asynTrace?
>
> I suspect the device is actually returning 16-bit binary data, which is the most common Modbus data type.
>
> You need to look at the Omega manual to determine:
>
> - How many bits is the data (12, 14, 16, etc.)
> - What binary format does it use (2's complement, sign and offset, etc.)
>
> I took a quick look at the Omega iSeries communications manual:
>
> http://www.omega.com/manuals/manualpdf/M3397.pdf
>
> It has a reasonable description of their Modbus protocol. However, I could not find a description of how they handle signed numbers - 2's complement or sign and offset.
>
> You should then use a record definition like the following:
>
> # ai record template for register inputs
> record(ai, "$(P)$(R)") {
> field(DTYP,"asynInt32")
> field(INP,"@asynMask($(PORT) $(OFFSET) $(BITS))INT16")
> field(LINR,"LINEAR")
> field(EGUL,"$(EGUL)")
> field(EGUF,"$(EGUF)")
> field(HOPR,"$(EGUF)")
> field(LOPR,"$(EGUL)")
> field(PREC,"$(PREC)")
> field(SCAN,"$(SCAN)")
> }
>
> The UINT16 drvUser field assumes the device has signed 16-bit 2's complement data. Other possibilities are UINT16 (unsigned 16-bit integers), INT16SM (16-bit integers in sign-magnitude format), etc. This document provides more information:
>
> http://cars9.uchicago.edu/software/epics/modbusDoc.html
>
> Let me know if you have more questions or problems.
>
> Cheers,
> Mark
>
>
>
> -----Original Message-----
> From: [email protected] [mailto:[email protected]] On Behalf Of S. Banerian
> Sent: Monday, May 13, 2013 4:24 PM
> To: EPICS Tech Talk
> Subject: Modbus TCP and Omega
>
>
> I have an Omega CNi853-EIT device, with thermocouple attached, which can
> be accessed via Modbus TCP.
>
> I've been able to get an IOC to query the Omega, and it does reply, but
> it sends back its data as hex, so, e.g. 00 e6 is its representation for
> 230 (23.0 C).
>
> In my databases, I've tried mbbi bi and ai types, but probe tells me
> the PV is always in an "invalid" state.
>
> What would folks suggest I use to read this hex value?
>
>
--
Stefani Banerian
UW Clinical Cyclotron
UW School of Medicine
206-598-0302
gpg key 6642E7EE
fingerprint = BD13 875D 2D03 5E1D 1E3B 8BF7 F4B8 63AD 6642 E7EE
- Replies:
- RE: Modbus TCP and Omega Mark Rivers
- References:
- Modbus TCP and Omega S. Banerian
- RE: Modbus TCP and Omega Mark Rivers
- RE: Modbus TCP and Omega Mark Rivers
- Navigate by Date:
- Prev:
RE: Relative time in XY graph Chen, Xihui
- Next:
RE: Modbus TCP and Omega Mark Rivers
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
- Navigate by Thread:
- Prev:
RE: Modbus TCP and Omega Mark Rivers
- Next:
RE: Modbus TCP and Omega Mark Rivers
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025