1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 <2013> 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 <2013> 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: Using MEDM for timing |
From: | Mark Rivers <[email protected]> |
To: | "'nalaka samarasinghe'" <[email protected]>, "[email protected]" <[email protected]> |
Date: | Tue, 20 Aug 2013 15:17:00 +0000 |
I think you are asking the wrong question. You don’t need a special medm widget for that, the standard widgets can be used. You do probably need 2 things: 1) A feedback record. The EPICS epid record can be used for this. It can read the temperature from your readout device and control the power to a power supply using a D/A
converter, for example. 2) Some other record or client to control the setpoint of the feedback record. You could use the sscan record in table mode to generate an arbitrary temperature profile,
for example. Or you could use a client like Python, IDL, etc. I have attached a screen shot of one of our temperature control screens. At the time I took this screen shot the thermocouple was broken, so the temperature reading is meaningless,
but you get the idea. Mark From: [email protected] [mailto:[email protected]]
On Behalf Of nalaka samarasinghe Hi All, I need to use MEDM application for building a programmable temperature controller. That is the system should be able to heat some fluid at some pre determined temperature for a period and increase the temperature to a higher value and keep
it for some period. I could not find any widget that i can use for this application. It is appreciated if you could give me some guidance on the above. Thanks & Regards, Nalaka |