Experimental Physics and Industrial Control System
On the machine that is working type:
printenv | grep EPICS
at the shell and
epicsPrtEnvParams
at the IOC prompt.
On the machine that is not working do the same thing.
And on the machine that is not working at the shell do
caget SOME_PV_NAME
cainfo SOME_PV_NAME
It could be you will be able to access the PVs using the caget and cainfo commands, which use the C CA library, but not from CSS which uses the Java CA library. I think CSS uses a different mechanism to set EPICS_CA_ADDR_LIST, etc.
Mark
________________________________
From: Julio Calvo [[email protected]]
Sent: Thursday, November 28, 2013 10:31 AM
To: Mark Rivers; techtalkForo
Subject: Re: All Pvs disconnected
I have changed that variables but still not working.
I have the same configuration of that machine, here, and it works, without internet. And it is not connected, no cable.
Thanks.
Julio.
El Jueves 28 de noviembre de 2013 17:01, Mark Rivers <[email protected]> escribió:
If the Ethernet port is disconnected then CA does not work. I think if you set EPICS_CA_AUTO_ADDR_LIST=NO and EPICS_CA_ADDR_LIST=localhost it will work, but I am not certain.
You could also just plug the Ethernet cable into a cheap switch with nothing else connected to it :-)
Mark
________________________________
From: [email protected]<mailto:[email protected]> [[email protected]<mailto:[email protected]>] on behalf of Julio Calvo [[email protected]<mailto:[email protected]>]
Sent: Thursday, November 28, 2013 9:53 AM
To: techtalkForo
Subject: All Pvs disconnected
Hello,
I have move a computer from my lab, it was working perfectly, it was connected to internet, now, this computer is in other place without internet connection for security reasons. I have open the IOC, pvs are ok after dbl. But CSS GUI appears as disconnected, any idea?. I have done this several times and I never found this problem. Do I have to configure something?.
Thanks.
Julio.
- References:
- All Pvs disconnected Julio Calvo
- RE: All Pvs disconnected Mark Rivers
- Re: All Pvs disconnected Julio Calvo
- Navigate by Date:
- Prev:
Re: All Pvs disconnected Julio Calvo
- Next:
Re: Increasing scan rate to 10 kHz Benjamin Franksen
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: All Pvs disconnected Julio Calvo
- Next:
FW: All Pvs disconnected Mark Rivers
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024