1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 <2015> 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 <2015> 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: Alarm handling |
From: | "Arnold, Ned D." <[email protected]> |
To: | "[email protected]" <[email protected]> |
Date: | Thu, 10 Dec 2015 21:17:40 +0000 |
* Set all the records you want to process when the alarm occurs to *.SCAN=Event; EVNT=<reserved_event_1>
* Use a calcout record to monitor the records you want to respond to and the conditions on which to take action ... <importantPV1.SEVR> <importantPV2.SEVR> ... * set the "Out Event" field of the calcout record (OEVT) to <reserved_event_1> Numerous records will scan when your conditions are met. Ned From: [email protected] [[email protected]] on behalf of Henrique Almeida [[email protected]]
Sent: Thursday, December 10, 2015 02:54 PM To: [email protected] Talk Subject: Alarm handling Hello, what's the proper way to process a record if and only if another record raises an alarm ?
|