> On Dec 10, 2015, at 3:54 PM, Henrique Almeida <[email protected]> wrote:
>
>
> Hello, what's the proper way to process a record if and only if another record raises an alarm ?
Not sure about ‘proper’, but now way that allows you full control would be a calcout record.
INPA points to the *.SEVR field of the record you want to check.
OUT points to the record that you want to process.
In CALC you can check for A>0 or A== some specific severity level.
In the OOPT you can then use "Transition to Non-zero” to process when you have the desired alarm.
-Kay