Experimental Physics and Industrial Control System
On 03/06, Kasemir, Kay wrote:
> The 'caget' command will by default not show alarm detail, but when you use 'camonitor' you'll see the alarm.
> With 'caget', check 'caget -h' for the various request type options.
> Given a numeric record,
> caget -d DBR_STS_DOUBLE YourPVName
> will show the value with alarm status & severity.
Or use caget's "-a" option:
$ caget -a YourPVName
Lewis
- Replies:
- Re: Question related to PV record Vandana Yadav
- References:
- Question related to PV record Vandana Yadav
- RE: Question related to PV record Mark Rivers
- Re: Question related to PV record Kasemir, Kay
- Navigate by Date:
- Prev:
Re: Question related to PV record Kasemir, Kay
- Next:
Stream device question Luchini, Kristi L.