1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 <2019> 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 <2019> 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Question about rdb channel archive |
From: | Florian Feldbauer via Tech-talk <[email protected]> |
To: | [email protected] |
Date: | Wed, 20 Feb 2019 16:23:27 +0100 |
Dear Zhefu,I don't know it the monitor threshold within the archive engine works the same as the ADEL field within EPICS records.
For EPICS PVs, to send everything even if there is no change, the ADEL field should be '-1'. '0' means at least 1 bit in VAL has to change.
Hope this helps. Best regards, Florian On 2/20/19 4:11 PM, lzf neu via Tech-talk wrote:
Dear Dr. Kay, For special purposes, I intend to let the archive engine write real time data to database every monitor period (my period is 1.0s), irrespective of whether the real time data changed. I tried to set the XML configuration file for a monitor with engine enforced value change threshold of 0.0 as follows: <channel> <name>NSV:P2</name> <period>1.0</period> <monitor>0.0</monitor></channel> However, I faild. I have no idea how to achieve the goal. Any help will be appreciated and thanks in advance. Zhefu
-- Dr. Florian Feldbauer Ruhr-Universität Bochum Experimentalphysik I AG Universitätsstr. 150 Fach-Nr. 125 D-44801 Bochum Office: NB 2/134 Phone: (+49)234 / 32-23563 Fax: (+49)234 / 32-14170 https://paluma.ruhr-uni-bochum.de