1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: AlarmServer: No Connection and UNDEFINED
From: LiuP via Tech-talk <tech-talk at aps.anl.gov>
To: <tech-talk at aps.anl.gov>
Date: Fri, 17 Apr 2020 15:57:35 +0800

 

Hi, All:

 

Can you give me some advice about the confusion of alarmserver-4.5.0?

I downloaded the alarmserver-4.5.0/jms2rdb-4.5.0 and others from SNS website. After some necessary process done, such as MariaDB dababase, activemq etc, I run the alarm server, jms server successfully.

Then add one EPICS PV bl:aiExamplin CSS-4.6.4 Alarm Tree, it work well. I can see the alarm state changes and I can  acknowledge the alarm state. But when I add another PV (X05U1:FM:TC) , it failed. The alarm tree or alarm table shows: the alarm severity undefined, the alarm message no connection.

What's the diffent between the two PVs?

The softIOC of the first one bl:aiExampl,  the Alarm Server and the CSS/OPI client are on same network.  In other words, their IP-addr are 10.30.50.XX1, 10.30.50.XX2, 10.30.50.XX3 .

The softIOC of the second one (X05U1:FM:TC) is on the other network: 10.30.78.YY, the port is 5066. But the two network section can be connected each other through network gateway. I can caget the two PVs at Alarm Server computer or CSS client computer correctly. I can sure the "HIGH, LOW, HSV, LSV ….." fields of these records are set ok.

I think the right way is  to modify the plugin_customization.ini file:

find the "# Channel Access" section, and modify the addr_list from 127.0.0.1 to 10.30.78.246:5066

         org.csstudio.platform.libs.epics/addr_list="10.30.78.246:5066"

 

But still failed. How to fix it? 

 

Thank you!

 


LIU Ping

SSRFCHINA


Replies:
Re: [EXTERNAL] AlarmServer: No Connection and UNDEFINED Kasemir, Kay via Tech-talk

Navigate by Date:
Prev: Re: PolyScience Model 4100 and 4200 Series Liquid-to-Liquid Coolers Hu, Yong via Tech-talk
Next: Re: [EXTERNAL] AlarmServer: No Connection and UNDEFINED Kasemir, Kay via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024 
Navigate by Thread:
Prev: How to use SRQ from device in StreamDevice. Noboru Yamamoto via Tech-talk
Next: Re: [EXTERNAL] AlarmServer: No Connection and UNDEFINED Kasemir, Kay via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  <20202021  2022  2023  2024