>>> dbpr("XX:CALC",2)
A: 0 ACKS: NO_ALARM ACKT: YES ADEL: 0
ASG: B: 42 BKPT: 00 C: 0
CALC: A*B D: 0 DESC: DISA: 0
DISP: 0 DISS: NO_ALARM DISV: 1 DTYP: <nil>
E: 0 EGU: EVNT: 0 F: 0
FLNK:CONSTANT 0 G: 0 H: 0 HHSV: NO_ALARM
HIGH: 0 HIHI: 0 HOPR: 0 HSV: NO_ALARM
HYST: 0 I: 0 INPA:DB_LINK XX:VALUE NPP NMS
INPB:CONSTANT INPC:CONSTANT INPD:CONSTANT INPE:CONSTANT
INPF:CONSTANT INPG:CONSTANT INPH:CONSTANT INPI:CONSTANT
INPJ:CONSTANT INPK:CONSTANT INPL:CONSTANT J: 0
K: 0 L: 0 LCNT: 0 LLSV: NO_ALARM
LOLO: 0 LOPR: 0 LOW: 0 LSV: NO_ALARM
MDEL: 0 NAME: XX:CALC NSEV: NO_ALARM NSTA: NO_ALARM
PACT: 0 PHAS: 0 PINI: NO PREC: 0
PRIO: LOW PUTF: 0 RPRO: 0 SCAN: Passive
SDIS:CONSTANT SEVR: INVALID STAT: UDF TIME: <undefined>
TPRO: 0 TSE: 0 TSEL:CONSTANT UDF: 1
VAL: 0
>>> dbpr("XX:VALUE",2)
ACKS: NO_ALARM ACKT: YES ADEL: 0 AOFF: 0
ASG: ASLO: 1 BKPT: 00 DESC:
DISA: 0 DISP: 0 DISS: NO_ALARM DISV: 1
DTYP: Python EGU: EGUF: 0 EGUL: 0
EOFF: 0 ESLO: 1 EVNT: 0 FLNK:DB_LINK XX:CALC
HHSV: NO_ALARM HIGH: 0 HIHI: 0 HOPR: 0
HSV: NO_ALARM HYST: 0 INP:INST_IO @XX:VALUE
LCNT: 0 LINR: NO CONVERSION LLSV: NO_ALARM LOLO: 0
LOPR: 0 LOW: 0 LSV: NO_ALARM MDEL: 0
NAME: XX:VALUE NSEV: NO_ALARM NSTA: NO_ALARM PACT: 0
PHAS: 0 PINI: NO PREC: 0 PRIO: LOW
PUTF: 0 ROFF: 0 RPRO: 0 RVAL: 0
SCAN: I/O Intr SDIS:CONSTANT SEVR: INVALID SIML:CONSTANT
SIMM: NO SIMS: NO_ALARM SIOL:CONSTANT SMOO: 0
STAT: UDF SVAL: 0 TIME: <undefined> TPRO: 0
TSE: 0 TSEL:CONSTANT UDF: 0 VAL: 7
>>>
On Fri, Feb 5, 2021 at 1:48 PM Johnson, Andrew N. <anj at anl.gov> wrote:
Sounds like you still need a Python softIoc expert then.
It might be helpful if you post the output of
dbpr("XX:CALC", 2)
and
dbpr("XX: VALUE", 2)
though so we can see what it sets all the fields to though.
- Andrew
On Feb 5, 2021, at 1:39 PM, Paul Nord <Paul.Nord at valpo.edu> wrote:
Andrew,
That loads without error. But the calculation doesn't actually work.
#!/usr/local/epics/modules/pythonIoc/pythonIoc
from softioc import softioc, builder
builder.SetDeviceName('XX')
rec = builder.aIn('VALUE',VAL=3)
calc = builder.records.calc('CALC', CALC = 'A*B', INPA = rec, B = 42)
rec.FLNK = builder.PP(calc)
#run the ioc
builder.LoadDatabase()
softioc.iocInit()
#start the ioc shell
softioc.interactive_ioc(globals())
===========
$ caput "XX:VALUE" 7
Old : XX:VALUE 3
New : XX:VALUE 7
$ caget "XX:CALC"
XX:CALC 0
===========
>> dbpr("XX:CALC")
A: 0 ASG: B: 42 C: 0
CALC: A*B D: 0 DESC: DISA: 0
DISP: 0 DISV: 1 E: 0 F: 0
G: 0 H: 0 I: 0 J: 0
K: 0 L: 0 NAME: XX:CALC SEVR: INVALID
STAT: UDF TPRO: 0 VAL: 0
On Fri, Feb 5, 2021 at 1:27 PM Johnson, Andrew N. <anj at anl.gov> wrote:
Hi Paul,
On Feb 5, 2021, at 12:23 PM, Paul Nord via Tech-talk <tech-talk at aps.anl.gov> wrote:
According to the documentation, this should work:
#!/usr/local/epics/modules/pythonIoc/pythonIoc
from softioc import softioc, builder
builder.SetDeviceName('XX')
rec = builder.aIn('VALUE')
calc = builder.records.calc('CALC', CALC = 'A*B', A = rec, B = 42)
rec.FLNK = builder.PP(calc)
I’ve never used the Python softIoc, but given this error message
AssertionError: Can't write "XX:VALUE" to field A: not a number
have you tried this instead?
calc = builder.records.calc('CALC', CALC = 'A*B', INPA = rec, B = 42)
- Andrew
--
Complexity comes for free, simplicity you have to work for.
--