1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Dynamic user limits in softMotor
From: Laurenz Rettig via Tech-talk <tech-talk at aps.anl.gov>
To: tech-talk at aps.anl.gov
Date: Fri, 5 Feb 2021 23:45:53 +0100
Hi,

I've set up a softMotor record that converts between coordinate systems
according to some user-definable parameters according to some soft-ioc
ai records using a CALC record. That works all nice and pretty, however
what I did not get to work is to also set the soft-limits of the
softMotor dynamically to the corresponding ai record values.

This is my Soft-Motor and ai-record definition:

record(motor,"$(IOC):$(powerMotor)")
{
    field(DTYP,"Soft Channel")
    field(OUT,"$(IOC):$(convertPowerToWp).A  PP MS")
    field(RDBL,"$(IOC):$(convertWpToPower).VAL  NPP MS")
    field(URIP,"Yes")
    field(STOO,"$(IOC):$(wpMotor).STOP  PP MS")
    field(DINP,"$(IOC):$(wpMotor).DMOV  NPP MS")
    field(MRES,0.001)
    field(RRES,1)
    field(PREC,3)
    field(DHLM,"$(IOC):$(MaxPower).VAL CP MS")
    field(DLLM,"$(IOC):$(MinPower).VAL CP MS")
    field(TWV,".1")
    field(RTRY,"0")
    field(EGU,"W")
}

record(ai,"$(IOC):$(MinPower)")
{
    info(autosaveFields, "VAL")
    field(DESC,"Minimum Power")
    field(VAL,"0")
    field(FLNK,"$(IOC):$(convertWpToPower) PP MS")
    field(EGU,"W")
}

record(ai,"$(IOC):$(MaxPower)")
{
    info(autosaveFields, "VAL")
    field(DESC,"Maximum Power")
    field(VAL,"1")  
    field(FLNK,"$(IOC):$(convertWpToPower) PP MS")
    field(EGU,"W")
}

And the errors I get:

Can't set "simManip:Pump:Power.DHLM" to "simManip:Pump:MaxPower.VAL CP
MS" No digits to convert
Can't set "simManip:Pump:Power.DLLM" to "simManip:Pump:MinPower.VAL CP
MS" No digits to convert

I would appreciate any advice on this.

Thanks, Laurenz

-- 
Dr. Laurenz Rettig
Fritz Haber Institute of the Max Planck Society
Department of Physical Chemistry
Dynamics of Correlated Materials
Faradayweg 4-6
14195 Berlin, Germany

phone: +49-(0)30-8413 5225
email: rettig at fhi-berlin.mpg.de



Replies:
Re: Dynamic user limits in softMotor Mooney, Tim M. via Tech-talk

Navigate by Date:
Prev: RE: Question about databrowser of CSS Manoussakis, Adamandios via Tech-talk
Next: Re: Creating calc record in Python softioc Paul Nord via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
Navigate by Thread:
Prev: Re: Creating calc record in Python softioc Jaroslav Adam via Tech-talk
Next: Re: Dynamic user limits in softMotor Mooney, Tim M. via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
ANJ, 06 Feb 2021 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·