1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: AD Stats with URL camera Profile problem
From: Mark Rivers via Tech-talk <tech-talk at aps.anl.gov>
To: "Smith, William" <william.smith at helmholtz-berlin.de>
Cc: "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Tue, 24 Aug 2021 01:42:57 +0000
You need to set the $(XSIZE) and $(YSIZE) macro variables in your st.cmd file to the maximum X andY size of your image. This is documented in EXAMPLE_commonPlugins.cmd.

Mark


Sent from my iPhone

On Aug 23, 2021, at 2:02 PM, Smith, William via Tech-talk <tech-talk at aps.anl.gov> wrote:


Hi,

I am using AD Stats plugin to determine the profile of a spot in an image. If I try and use a URL camera (Specifically an AXIS M114 camera) Then the profile is at most length 640  in the x dimension and 480 in the y, even if the image dimensions are greater than that. If I reduce the image size in the camera settings (not in area detector, but the camera itself) to an image size at or below 640x480, then the profile in x or y is that length.

I am able to plot the image from the StdArray plugin and I can see that it is the correct size. The image size is also reported correctly by $(P)cam1:ArraySizeX_RBV and $(P)cam1:ArraySizeY_RBV

Has anybody seen anything like this before? If I use this with the simDetector I have no problems, the profile length in each axis scales with the image size as expected.

Many thanks,

Will

________________________________

Helmholtz-Zentrum Berlin für Materialien und Energie GmbH

Mitglied der Hermann von Helmholtz-Gemeinschaft Deutscher Forschungszentren e.V.

Aufsichtsrat: Vorsitzender Dr. Volkmar Dietz, stv. Vorsitzende Dr. Jutta Koch-Unterseher
Geschäftsführung: Prof. Dr. Jan Lüning (Sprecher), Prof. Dr. Bernd Rech, Thomas Frederking

Sitz Berlin, AG Charlottenburg, 89 HRB 5583

Postadresse:
Hahn-Meitner-Platz 1
14109 Berlin
Deutschland

References:
AD Stats with URL camera Profile problem Smith, William via Tech-talk

Navigate by Date:
Prev: AD Stats with URL camera Profile problem Smith, William via Tech-talk
Next: LIB_LIBS getting ignored Jones, Edward (CODAS&IT) via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024 
Navigate by Thread:
Prev: AD Stats with URL camera Profile problem Smith, William via Tech-talk
Next: LIB_LIBS getting ignored Jones, Edward (CODAS&IT) via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  <20212022  2023  2024