On 5/24/22 08:20, Wang, Andrew via Tech-talk wrote:
> Hi all,
>
> Suppose I have an IOC called foo that contains an analog input record called foo_record and I have another IOC called bar. Is there a possible way to input a value into foo_record when bar is exited? For instance, if I exit bar, I want foo_record to have a certain value.
A link with the CP modifier will alarm with INVALID severity while disconnected.
And you can use that in combination with the IVOA/IVOV mechanics of an output record to write a specific value into a specific place.