Hm,
I think I have lost track about the connection between records and asyn parameters.
I am missing the name of the parameter here:
> > record(bo,"$(P)$(R)-TC1_enable") {
> > field(DTYP,"asynUInt32Digital")
> > field(OUT,"@asynMask($(PORT), 0, 0x8000 )")
> field(OUT,"@asynMask($(PORT), 0, 0x8000 )SomeName")
> > field(ZNAM,"Disabled")
> > field(ONAM,"Enabled")
> > }
(Or isn’t that used in modbus ? I am confused)
The other question:
If I understand it rigth, you define output records.
And when the IOC starts, they should get their values from the
device, whatever is the actual value here, should be reflected in the record.
In that sense, I am missing these fields in the record definition:
info(asyn:INITIAL_READBACK,"1”)
info(asyn:READBACK,"1”)
Or do I miss something ?
/Torsten
> On 14 Apr 2023, at 20:57, Dale Cox <dale.cox at acu.edu> wrote:
>
> Torsten,
>
> Here it is:
>
> epics> asynReport 10 Z8TC1_Config
> Z8TC1_Config multiDevice:Yes canBlock:Yes autoConnect:Yes
> enabled:Yes connected:Yes numberConnects 1
> nDevices 4 nQueued 0 blocked:No
> asynManagerLock:No synchronousLock:No
> exceptionActive:No exceptionUsers 0 exceptionNotifys 0
> traceMask:0x1 traceIOMask:0x0 traceInfoMask:0x1
> interposeInterfaceList
> asynOctet pinterface 0x7f2974234460 drvPvt 0x555800dc6c50
> interfaceList
> asynCommon pinterface 0x7f2974234d10 drvPvt 0x555800dc5170
> asynDrvUser pinterface 0x7f2974234aa0 drvPvt 0x555800dc5170
> asynOctet pinterface 0x7f2974234be0 drvPvt 0x555800dc5170
> asynUInt32Digital pinterface 0x7f2974234c60 drvPvt 0x555800dc5170
> asynInt32 pinterface 0x7f2974234ce0 drvPvt 0x555800dc5170
> asynInt64 pinterface 0x7f2974234ca0 drvPvt 0x555800dc5170
> asynFloat64 pinterface 0x7f2974234c40 drvPvt 0x555800dc5170
> asynInt32Array pinterface 0x7f2974234b80 drvPvt 0x555800dc5170
> addr 0 autoConnect Yes enabled Yes connected Yes exceptionActive No
> exceptionActive No exceptionUsers 0 exceptionNotifys 0
> blocked No
> traceMask:0x1 traceIOMask:0x0 traceInfoMask:0x1
> addr 1 autoConnect Yes enabled Yes connected Yes exceptionActive No
> exceptionActive No exceptionUsers 0 exceptionNotifys 0
> blocked No
> traceMask:0x1 traceIOMask:0x0 traceInfoMask:0x1
> addr 2 autoConnect Yes enabled Yes connected Yes exceptionActive No
> exceptionActive No exceptionUsers 0 exceptionNotifys 0
> blocked No
> traceMask:0x1 traceIOMask:0x0 traceInfoMask:0x1
> addr 3 autoConnect Yes enabled Yes connected Yes exceptionActive No
> exceptionActive No exceptionUsers 0 exceptionNotifys 0
> blocked No
> traceMask:0x1 traceIOMask:0x0 traceInfoMask:0x1
> modbus port: Z8TC1_Config
> initialized: true
> asynOctet server: SenecaBus
> modbusSlave: 5
> modbusFunction: 6
> modbusStartAddress: 065
> modbusLength: 04
> absoluteAddressing: false
> dataType: 4 (UINT16)
> plcType: SenecaZ
> I/O errors: 0
> Read OK: 1
> Write OK: 0
> pollDelay: 0.400000
> Time for last I/O 21 msec
> Max. I/O time: 21 msec
> Time per hist. bin: 1 msec
> Port: Z8TC1_Config
> Timestamp: <undefined>
> Input EOS[0]:
> Output EOS[0]:
> Parameter list 0
> Number of parameters is: 12
> Parameter 0 type=asynInt32, name=MODBUS_DATA, value is undefined
> Parameter 1 type=asynInt32, name=MODBUS_READ, value is undefined
> Parameter 2 type=asynUInt32Digital, name=ENABLE_HISTOGRAM, value is undefined
> Parameter 3 type=asynInt32, name=READ_HISTOGRAM, value is undefined
> Parameter 4 type=asynInt32, name=HISTOGRAM_BIN_TIME, value is undefined
> Parameter 5 type=asynInt32Array, name=HISTOGRAM_TIME_AXIS, value is undefined
> Parameter 6 type=asynFloat64, name=POLL_DELAY, value is undefined
> Parameter 7 type=asynInt32, name=READ_OK, value=1, status=0
> Parameter 8 type=asynInt32, name=WRITE_OK, value=0, status=0
> Parameter 9 type=asynInt32, name=IO_ERRORS, value=0, status=0
> Parameter 10 type=asynInt32, name=LAST_IO_TIME, value=21, status=0
> Parameter 11 type=asynInt32, name=MAX_IO_TIME, value=21, status=0
>
> On Fri, Apr 14, 2023 at 1:46 PM Torsten Bögershausen <torsten.bogershausen at ess.eu> wrote:
> I have the slight feeling, but this is a shot into the blue,
> that the driver is doing the right thing.
> And may be the record is initialized to early ?
>
> What does
> asynReport 10 Z8TC1_Config
> give you ?
>
> Do you see the right values in the asynparameters ?
>
>
>
> > On 14 Apr 2023, at 15:43, Dale Cox via Tech-talk <tech-talk at aps.anl.gov> wrote:
> >
> > Thanks for the reply Mark.
> >
> > (1) Yes I thought this was the case. Whenever I enable some asyn trace lines in the IOC, I can see the initial modbus request. It looks like this:
> >
> > ...
> > drvModbusAsynConfigure("Z8TC1_Config", "SenecaBus", 5, 6, 53, 4, "UINT16", 400, "SenecaZ")
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort locking port
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort created queueLockPortPvt=0x55ec3aba5df0
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort created queueLockPortPvt=0x55ec3aba5df0, event=0x55ec3aba5e10, mutex=0x55ec3aba5eb0
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort taking mutex 0x55ec3aba5eb0
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort queueing request
> > 2023/04/14 08:32:01.482 SenecaBus addr -1 queueRequest priority 0 not lockHolder
> > 2023/04/14 08:32:01.482 SenecaBus schedule queueRequest timeout in 2.000000 seconds
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort waiting for event
> > 2023/04/14 08:32:01.482 asynManager::portThread port=SenecaBus callback
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPortCallback signaling begin event
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPortCallback waiting for mutex from queueUnlockPort
> > 2023/04/14 08:32:01.482 SenecaBus asynManager::queueLockPort got event from callback
> > 2023/04/14 08:32:01.482 SenecaBus flush
> > 2023/04/14 08:32:01.482 /dev/ttyUSB0 flush
> > 2023/04/14 08:32:01.487 /dev/ttyUSB0 write.
> > 2023/04/14 08:32:01.487 /dev/ttyUSB0 write 8
> >
> > 05 03 00 35 00 04 55 83
> > 2023/04/14 08:32:01.487 wrote 8 to /dev/ttyUSB0, return asynSuccess
> > 2023/04/14 08:32:01.487 asynOctetSyncIO wrote:
> >
> > 05 03 00 35 00 04
> > 2023/04/14 08:32:01.487 /dev/ttyUSB0 read.
> > 2023/04/14 08:32:01.495 /dev/ttyUSB0 read 13
> >
> > 05 03 08 d0 11 d2 00 d2 00 d2 11 3b 1c
> > 2023/04/14 08:32:01.495 /dev/ttyUSB0 read 13, return 0
> > 2023/04/14 08:32:01.495 SenecaBus read 13 bytes eom=0
> >
> > 05 03 08 d0 11 d2 00 d2 00 d2 11 3b 1c
> > 2023/04/14 08:32:01.495 asynOctetSyncIO read:
> >
> > 03 08 d0 11 d2 00 d2 00 d2 11
> > 2023/04/14 08:32:01.495 SenecaBus queueUnlockPort
> > 2023/04/14 08:32:01.495 SenecaBus asynManager::queueUnlockPort waiting for event
> > 2023/04/14 08:32:01.495 SenecaBus queueUnlockPort unlock mutex 0x55ec3aba5eb0 complete.
> > ...
> >
> > So I'm getting the requested registers back on that port, and you can see their values there. d0 11 is 1101000000010001 in binary, so when I look at the 15th bit, it should return back a 1. when I do a caget on that PV, I get a 0 (I get 0's for all of the records associated with these registers).
> >
> > Is it supposed to say "asynSuccess" at the end of the highlighted section? I get a "return 0".
> >
> >
> > Thanks for helping me troubleshoot.
> >
> > Dale
> >
> >
> > On Thu, Apr 13, 2023 at 4:38 PM Mark Rivers <rivers at cars.uchicago.edu> wrote:
> > Hi Dale,
> >
> >
> >
> > • My issue is that the PV values aren't being updated when the IOC starts -- meaning that after the IOC start, the bo and mbbo values stored in that register don't match what was returned via the initial modbus request.
> >
> >
> > I am not sure I completely understand what you are saying. Here is what should happen:
> >
> >
> >
> > • Because this port you created uses function code 6 (write single register) and because you have a non-zero poll time, the driver will do one initial read of that register using function code 3.
> > • EPICS device support for the bo records does a read operation from the port during init_record. If this read returns asynSuccess (which it should) then the value of the bo record is set to the value read from the driver. This is the “bumpless reboot” concept.
> > • You have not set PINI=YES in these records, so the value from the record will not be written back to the device during iocInit. However, the record value should still match the device, because of steps 1 and 2 above.
> >
> >
> > If I understand correctly you are saying that the bo record does have the correct value read from the device during steps 1-2. But now the device has a different value from that in the record? I don’t understand that, since it seems like there must have been a write to the device to change the value?
> >
> >
> >
> > Mark
> >
> >
> >
> >
> >
> > From: Tech-talk <tech-talk-bounces at aps.anl.gov> On Behalf Of Dale Cox via Tech-talk
> > Sent: Thursday, April 13, 2023 8:29 AM
> > To: tech-talk at aps.anl.gov
> > Subject: modbus ioc start
> >
> >
> >
> > Good Morning,
> >
> >
> >
> > I have an IOC that is currently reading registers via modbus rtu over rs485. There are a set of registers that store multiple configuration options in a single register. I set up the port using this line:
> >
> >
> >
> > > drvModbusAsynConfigure("Z8TC1_Config", "SenecaBus", 5, 6, 53, 4, "UINT16", 100, "SenecaZ")
> >
> >
> >
> > I've enabled the debugging lines on this IOC. When the IOC starts, I can see that the correct registers are being retrieved when the port is created. I can also write config changes to those registers at their assigned PV's with no issues that I have found. My issue is that the PV values aren't being updated when the IOC starts -- meaning that after the IOC start, the bo and mbbo values stored in that register don't match what was returned via the initial modbus request.
> >
> >
> >
> > Here are a couple of the DB entries that I'm using:
> >
> >
> >
> > record(bo,"$(P)$(R)-TC1_enable") {
> > field(DTYP,"asynUInt32Digital")
> > field(OUT,"@asynMask($(PORT), 0, 0x8000 )")
> > field(ZNAM,"Disabled")
> > field(ONAM,"Enabled")
> > }
> >
> > record(bo,"$(P)$(R)-TC2_enable") {
> > field(DTYP,"asynUInt32Digital")
> > field(OUT,"@asynMask($(PORT), 0, 0x4000 )")
> > field(ZNAM,"Disabled")
> > field(ONAM,"Enabled")
> > }
> >
> > record(bo,"$(P)$(R)-TC1-2_units") {
> > field(DTYP,"asynUInt32Digital")
> > field(OUT,"@asynMask($(PORT), 0, 0x2000 )")
> > field(ZNAM,"tempDegC")
> > field(ONAM,"mV")
> > }
> >
> >
> >
> > Any help is appreciated.
> >
> >
> >
> > Dale
> >
> >
> >
> > --
> >
> > Dale Cox
> >
> > Instrumentation and Electrical Engineer
> >
> > ACU NEXT Lab
> >
>
- Replies:
- RE: modbus ioc start Mark Rivers via Tech-talk
- References:
- modbus ioc start Dale Cox via Tech-talk
- RE: modbus ioc start Mark Rivers via Tech-talk
- Re: modbus ioc start Dale Cox via Tech-talk
- Re: modbus ioc start Torsten Bögershausen via Tech-talk
- Re: modbus ioc start Dale Cox via Tech-talk
- Navigate by Date:
- Prev:
Re: modbus ioc start Dale Cox via Tech-talk
- Next:
RE: modbus ioc start Mark Rivers via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
<2023>
2024
- Navigate by Thread:
- Prev:
Re: modbus ioc start Dale Cox via Tech-talk
- Next:
RE: modbus ioc start Mark Rivers via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
<2023>
2024