Hi,
I noticed inconsistent behavior across different records after setting
the PINI field. For my understanding, if the PINI field is set to YES,
the record should be process with an initial value of 0.
The db file (tested with R7.0.8 softIocPVA)
record(bo, "bo"){
field(PINI, "YES")
}
record(aao, "aao"){
field(PINI, "YES")
}
record(ao, "ao"){
field(PINI, "YES")
}
record(longout, "lo"){
field(PINI, "YES")
}
record(stringout, "so"){
field(PINI, "YES")
}
record(mbbo, "mbbo") {
field(PINI, "YES")
}
record(mbbo, "mbboval") {
field(PINI, "YES")
field(VAL, "0")
}
record(mbboDirect, "mbbodir"){
field(PINI, "YES")
}
I checked the value of UDF and TIME. I think if TIME field has a value
then that means this record is processed. I also tried PINI=RUNNING, got
the same result.
Are there any specific reasons why mbbo/mbboDirect are not being
processed? Why UDF is cleared only for ao/aao?
ao, UDF: 0, TIME: OK
aao, UDF: 0, TIME: OK
bo, UDF: 1, TIME: OK
longout, UDF: 1, TIME: OK
stringout, UDF: 1, TIME: OK
mbbo, UDF: 1, TIME: undefined
mbbo (Set VAL manually), UDF: 0, TIME: OK
mbboDirect, UDF: 1, TIME: undefined
Cheers,
Di Wang
- Navigate by Date:
- Prev:
Re: AW: Readback of output variables in adsDriver Torsten Bögershausen via Tech-talk
- Next:
AW: AW: Readback of output variables in adsDriver Meyer, Markus via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
<2024>
- Navigate by Thread:
- Prev:
Re: Epics Integration with Allen Bradley 1769-L33ER PLC Hovanes Egiyan via Tech-talk
- Next:
Disable output record using asynInt32 interface automatic read from the hardware Yann Mandza via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
<2024>