I have another question. What does EPICS base do when the process() routine for an input record returns an error? Is there a specific error code it should return, or is any non-zero value OK?
Mark
-----Original Message-----
From: Mark Rivers
Sent: Thursday, October 01, 2015 9:51 AM
To: 'Ralph Lange'
Cc: EPICS Core-Talk
Subject: RE: ASYN Device Support Issue
Hi Ralph,
What version of asyn are you using?
Does the record correctly set the alarm status when the queueRequest fails? I think it should.
The github master branch already has a change so that there are only messages printed when queueRequest first fails and then another when it succeeds again.
Here is a possible fix to the problems you found (i.e. returning success and setting value when queueRequest fails)
diff --git a/asyn/devEpics/devAsynInt32.c b/asyn/devEpics/devAsynInt32.c
index 054cf83..162c932 100644
--- a/asyn/devEpics/devAsynInt32.c
+++ b/asyn/devEpics/devAsynInt32.c
@@ -1075,18 +1075,19 @@ static long processMbbi(mbbiRecord *pr)
if(pPvt->canBlock) pr->pact = 0;
reportQueueRequestStatus(pPvt, status);
}
- pr->rval = pPvt->result.value & pr->mask;
- pr->time = pPvt->result.time;
if(pPvt->result.status==asynSuccess) {
pr->udf=0;
+ pr->rval = pPvt->result.value & pr->mask;
+ pr->time = pPvt->result.time;
}
else {
pasynEpicsUtils->asynStatusToEpicsAlarm(pPvt->result.status, READ_ALARM, &pPvt->alarmStat,
INVALID_ALARM, &pPvt->alarmSevr);
(void)recGblSetSevr(pr, pPvt->alarmStat, pPvt->alarmSevr);
}
+ status = pPvt->result.status;
pPvt->result.status = asynSuccess;
- return 0;
+ return status;
}
reportQueueRequestStatus() copies "status" into pPvt->result.status, so pPvt->result.status will contain the result of pasynManager->queueRequest().
If queueRequest succeeds then pPvt->result.status will contain either the status returned by pDriver->pasynInt32->read(), or by the pasynUser->auxStatus field for an interrupt callback.
My change would leave both the rval and the timestamp unmodified whenever pPvt->result.status is not asynSuccess. Is this correct? Should the timestamp also be left unchanged if there is an error?
The code at the end is needed because we want to return the status, but for reasons I don't recall we need to set pPvt->result.status back to asynSuccess before returning.
Mark
-----Original Message-----
From: Ralph Lange [mailto:[email protected]]
Sent: Thursday, October 01, 2015 8:08 AM
To: Mark Rivers
Cc: EPICS Core-Talk
Subject: ASYN Device Support Issue
Hi Mark,
The processRrrr() routines of the ASYN Device support for input records
always set the VAL (or RVAL) field and return success, even if the call
to queueRequest() acquiring the value fails.
In our case, with a non-blocking ASYN driver for a PXIe board, the RVAL
field of the mbbi record showing the board status is always set to 0 (=
"OK"), even when there is no such board present and the device never
connects.
We are pre-setting the database with 4 = "no board", but that gets
overwritten with 0 ="OK" at every processing.
That doesn't seem right, does it?
Shouldn't the process routine leave the value unchanged and return an
error when reading fails?
Thanks a lot,
~Ralph
- Replies:
- Re: ASYN Device Support Issue Andrew Johnson
- References:
- ASYN Device Support Issue Ralph Lange
- RE: ASYN Device Support Issue Mark Rivers
- Navigate by Date:
- Prev:
RE: ASYN Device Support Issue Mark Rivers
- Next:
Re: ASYN Device Support Issue Andrew Johnson
- Index:
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
<2015>
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: ASYN Device Support Issue Mark Rivers
- Next:
Re: ASYN Device Support Issue Andrew Johnson
- Index:
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
<2015>
2016
2017
2018
2019
2020
2021
2022
2023
2024