Experimental Physics and Industrial Control System
MEDM version 3.03 :
When I defined only three states for a mbbo record,
the following warning message will pop up whenever CA is
connected.
menuUpdateValueCb: Got state 3.
Only have strings for 3 states (starting at 0).
Kate:Mset_formatmode
A minor patch stops the warining message:
diff -c -u medmMenu.c.orig medmMenu.c
--- medmMenu.c.orig Tue Jun 10 12:13:27 2003
+++ medmMenu.c Thu Nov 29 07:24:48 2007
@@ -510,7 +510,7 @@
XmNnumChildren,&numChildren,
NULL);
i = (int) pr->value;
- if((i >=0) && (i < (int) numChildren)) {
+ if((i >=0) && (i <= (int) numChildren)) {
XtVaSetValues(widget,XmNmenuHistory,children[i],NULL);
} else {
medmPostMsg(1,"menuUpdateValueCb: Got state %d.\n"
Happy Hoildays to all!