1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Vxi11
From: "Szalata, Zenon M." <[email protected]>
To: "Mark Rivers" <[email protected]>
Cc: [email protected]
Date: Thu, 23 Jul 2009 14:50:28 -0700
I put these two commands in my st.cmd file:

asynSetTraceMask( "L0",10,0xff)
asynSetTraceIOMask( "L0",10,0x2) 

I assume that I did what you suggested.  I am not sure what is traceIOMask=255?

This is what I did:
1. Reboot the gateway,
2. Start IOC.  I get many trace messages.
3. Restart the IOC until it fails.  It failed on the fourth restart.  This time I got not one trace message.
4. I repeated the above and again on the fourth restart it failed.  Seems that some resource is being exhausted.

Thanks,
Zen

-----Original Message-----
From: Mark Rivers [mailto:[email protected]] 
Sent: Thursday, July 23, 2009 2:06 PM
To: Szalata, Zenon M.; [email protected]
Subject: RE: Vxi11

One suggestion would be to set asynTraceIOMask=2 and traceIOMask=255 for that asynPort in your startup script.  Then reboot the IOC until it fails and see if you can what is different in the traffic.

Mark

-----Original Message-----
From: [email protected]
[mailto:[email protected]] On Behalf Of Szalata, Zenon M.
Sent: Thursday, July 23, 2009 4:03 PM
To: [email protected]
Subject: Vxi11

I am using ICS 8065 Ethernet - GPIB gateway.  The soft IOC is built with EPICS R3.14.9, asyn version 4.11, streamdevice version 2.4.  Sometime when I restart the IOC it dies with the following error:


########################################################################
####
## EPICS R3.14.9-ilc3 $R3-14-9$ $2007/02/05 16:31:45$ ## EPICS Base built Mar  2 2009 ########################################################################
####
2009/07/23 13:28:10.304 L0 vxiCreateIrqChannel VXI: channel not established (create_intr_chan)
2009/07/23 13:28:10.304 L0 Warning -- SRQ not operational.

@@@ @@@ @@@ @@@ @@@
@@@ Received a sigChild for process 29220. The process was killed by signal 11 @@@ Current time: Thu Jul 23 13:28:10 2009


I don't understand these error messages.  I need to understand in what way the gateway is failing so that I can explain my problem more intelligently to the tech support at ICS.  So, my question is how to interpret the messages listed above?

Are there other users of the ICS 8065 gateway?  Has anyone seen this problem? If so what is the solution?

Thanks,
Zen



Replies:
Re: Vxi11 Eric Norum
References:
Vxi11 Szalata, Zenon M.
RE: Vxi11 Mark Rivers

Navigate by Date:
Prev: RE: Vxi11 Mark Rivers
Next: Re: Vxi11 Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Vxi11 Mark Rivers
Next: Re: Vxi11 Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024