Hi Emmanuel,
On 2012-03-08 Dirk Zimoch wrote:
> This looks strange. Are you sure that your link has the correct type,
> e.g. INST_IO, not CONSTANT, PV_LINK or CA_LINK or something like this?
>
> Do you check psi->inp.type before you parse the value?
This is important, and explains what you're seeing if the device support being
used for the record is the default "Soft Channel". When dbPutString() parses
a string for an INP or OUT field for which the device support selected says
the link type is CONSTANT (which is what soft channel support uses), the link
field becomes a struct pv_link. The first member of a struct pv_link is the
PV name extracted from that string, which ends at the first space character.
That matches what you're seeing:
> Emmanuel Mayssat wrote:
> >
> > It turns out this method doesn't work correctly anymore.
> > Indeed the psi->inp.value.instio.string is truncated at the first
> > 'space' char.
> > In my case, that means, it cannot scanf the 'df= ...'
> > I also noticed that I now have to include the '@' char, when before I
> > didn't have to.
Only the record's device support is supposed to be looking at that data. The
particular device support selected using the record's DTYP field controls what
kind of address to expect in the INP field using the device() DBD entry. Note
that in versions of Base before 3.14.12 the DTYP field of a record must be set
before its INP field in the .db file.
> > That change appeared between 3.14.8 and 3.14.11
> >
> > What is the correct way to read the INP field now?
It sounds to me that you need to write your own device support for the
stringin record which has the address type INST_IO.
- Andrew
--
Never interrupt your enemy when he is making a mistake.
-- Napoleon Bonaparte
- References:
- How to corretly read the INP field? Emmanuel Mayssat
- Re: How to corretly read the INP field? Dirk Zimoch
- Navigate by Date:
- Prev:
Converting driver of R3.13 Applications to R3.14 problems Bai Jiaoni
- Next:
Re: ASYN Communication through windows serial port (via USB) Josh Stein
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
<2012>
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: How to corretly read the INP field? Dirk Zimoch
- Next:
What's the status of EPICS on RTEMS? Feng Laurence
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
<2012>
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024