1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 <2012> 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 <2012> 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Channel Access problem over SSH |
From: | Pavel Masloff <[email protected]> |
To: | "Hill, Jeffrey O" <[email protected]> |
Cc: | EPICS Tech Talk <[email protected]> |
Date: | Tue, 17 Apr 2012 17:41:18 +0400 |
Hi Pavel,
online_notify.c:CA beacon (send to "172.20.255.255:5065") error was "Connection refused"
This probably indicates that the IOC’s IP kernel is unable locate a route to the beacon address 172.20.255.255.
To avoid this type of warning messages, one can modify the CA server beacon destination addresses, independent of the search message destination addresses, using EPICS_CA_AUTO_BEACON_ADDR_LIST and EPICS_CA_BEACON_ADDR_LIST. The server configuration chapter in the CA Reference Manual has some of the details.
Jeff
From: [email protected] [mailto:[email protected]] On Behalf Of Pavel Masloff
Sent: Saturday, April 07, 2012 12:19 AM
To: EPICS Tech Talk
Subject: Channel Access problem over SSH
Hello tech-talkers,
There is an example IOC on a linux machine (Fedora 16) with an IP-address 172.20.92.99/16:
$EPICS_CA_ADDR_LIST=172.20.92.99
$EPICS_CA_AUTO_ADDR_LIST=NO
Which means I can access PVs on the same machine where the IOC is running. It works. No problem.
Now, when I connect to the linux machine via SSH from another machine on the same subnet (Windows XP, Putty), and when I run the IOC from the SSH client, then I get the following message in epics shell (over Putty) every once in a while:
online_notify.c:CA beacon (send to "172.20.255.255:5065") error was "Connection refused"
Still the IOC is running, I can caget, caput, camonitor. The Firewall is off. What might be the case?
Pavel
--
Best regards,
Pavel Maslov, MS
Controls Engineer at Pulsed power Lab
Efremov Institute for Electro-Physical Apparatus
St. Petersburg, Russia
Mobile: +7 (951) 672 22 19
Phone: +7 (812) 461 01 01