1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 <2018> 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 <2018> 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | measComp 2-1 and TC32 |
From: | John Dobbins <[email protected]> |
To: | "[email protected]" <[email protected]> |
Date: | Wed, 19 Sep 2018 19:38:18 +0000 |
I am confused about the status of support for Measurement Computing TC32 on linux.
In
measComp-R2-1/measCompApp/src
the Makefile includes the lines:
PROD_IOC_WIN32 += testTC32
testTC32_SRCS += testTC32.c
ifeq (win32-x86, $(findstring win32-x86, $(T_A)))
testTC32_LIBS += cbw32
else ifeq (windows-x64, $(findstring windows-x64, $(T_A)))
testTC32_LIBS += cbw64
endif
but there is not a testTC32 IOC for linux. Is the TC32 supported by PROD_IOC_LINUX measCompApp ?
I tried running measCompApp with a single thermocouple.
The TC32 is connected via ethernet and configured to be Board# 1
Here is the IOC console on start-up:
jad22@erp201 $ ../../bin/linux-x86_64/measCompApp st.cmd
< envPaths
epicsEnvSet("IOC","iocTC32")
epicsEnvSet("TOP","/nfs/erl/online/epics/R3.15.5/support/measComp-R2-1")
epicsEnvSet("SUPPORT","/nfs/erl/online/epics/R3.15.5/support")
epicsEnvSet("ASYN","/nfs/erl/online/epics/R3.15.5/support/asyn4-33")
epicsEnvSet("CALC","/nfs/erl/online/epics/R3.15.5/support/calc-R3-7-1")
epicsEnvSet("STD","/nfs/erl/online/epics/R3.15.5/support/std-R3-4-1")
epicsEnvSet("MCA","/nfs/erl/online/epics/R3.15.5/support/mca-R7-7")
epicsEnvSet("BUSY","/nfs/erl/online/epics/R3.15.5/support/busy-R1-7")
epicsEnvSet("SSCAN","/nfs/erl/online/epics/R3.15.5/support/sscan-R2-11")
epicsEnvSet("AUTOSAVE","/nfs/erl/online/epics/R3.15.5/support/autosave-R5-9")
epicsEnvSet("SNCSEQ","/nfs/erl/online/epics/R3.15.5/support/seq-2.2.5")
epicsEnvSet("MEASCOMP","/nfs/erl/online/epics/R3.15.5/support/measComp-R2-1")
epicsEnvSet("EPICS_BASE","/nfs/erl/online/epics/R3.15.5/support/base-3.15.5")
## Register all support components
dbLoadDatabase "../../dbd/measCompApp.dbd"
measCompApp_registerRecordDeviceDriver pdbbase
# Configure port driver
# MultiFunctionConfig(portName, # The name to give to this asyn port driver
# boardNum, # The number of this board assigned by the Measurement Computing Instacal program
# maxInputPoints, # Maximum number of input points for waveform digitizer
# maxOutputPoints) # Maximum number of output points for waveform generator
#MultiFunctionConfig("TC32_1", 0, 1048576, 1048576)
MultiFunctionConfig("TC32_1", 1, 0, 0)
2018/09/19 15:13:53.411 MultiFunction::MultiFunction error, unknown board type=0
dbLoadTemplate("TC32.substitutions")
asynSetTraceIOMask TC32_1 -1 2
#asynSetTraceMask TC32_1 -1 255
#< save_restore.cmd
iocInit
Starting iocInit
############################################################################
## EPICS R3.15.5
## EPICS Base built Sep 19 2018
############################################################################
2018/09/19 15:13:53.916 MultiFunction:writeInt32, port TC32_1, function=14, ERROR writing 1 to address 1, status=1
2018/09/19 15:13:53.916 TC32:Ti0TCType devAsynInt32::processCallbackOutput process error
iocRun: All initialization complete
#create_monitor_set("auto_settings.req",30,"P=TC32:")
epics> dbl
TC32:Ti0Scale
TC32:Ti0TCType
TC32:Ti0Filter
TC32:Ti0
epics> dbpr TC32:Ti0
ASG: DESC: DISA: 0 DISP: 0
DISV: 1 NAME: TC32:Ti0 RVAL: 0 SEVR: NO_ALARM
STAT: NO_ALARM SVAL: 0 TPRO: 0 VAL: 0
epics>
InstaCall reports a reasonable temperature.
I am completely new to this device and to Measurement Computing support.
Any help appreciated.
John Dobbins