1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 <2019> 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 <2019> 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | FW: mbboDirect record setup |
From: | Mark Rivers via Tech-talk <[email protected]> |
To: | 'Pontius Pontiac' <[email protected]>, "'[email protected]'" <[email protected]> |
Date: | Thu, 15 Aug 2019 17:18:10 +0000 |
I forgot to CC tech-talk on my initial reply, so this message contains some discussion that is not previously on tech-talk. Ø
I assume mbboDirect requires consecutive bit addressing and there is no workaround to assign custom bit maps? That is correct, mmboDirect does require consecutive bit addressing. Mark From: Pontius Pontiac <[email protected]>
Hi Mark, Should I reply to the list? I couldn't find an obvious way to continue the thread, hence this reply directly to you. I'm new to tech-talk so if there is a convention to follow, please let me know.
An additional complication I came across is that the PLC we use, made by the company Acromag, groups output registers into 16-bit registers, of which only 4 bits correspond to outputs (the 12 MSBs are unused). Consequently, if I want to
control 6 mbboDirect bits, I found that I have to break this up into 4+2 bits. I assume mbboDirect requires consecutive bit addressing and there is no workaround to assign custom bit maps? Anyways I think the current situation is workable for us, thank you again for your prompt help! Best, Gautam On Wed, Aug 14, 2019 at 4:48 AM Mark Rivers <[email protected]> wrote:
|