1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Streamdevice reads weird 1 byte null data |
From: | Ralph Lange via Tech-talk <tech-talk at aps.anl.gov> |
To: | EPICS Tech Talk <tech-talk at aps.anl.gov> |
Date: | Fri, 15 Sep 2023 10:02:06 +0200 |
BTW: For binary protocols (using formats like %r or %R) using
Terminator/InTerminator is problematic because the binary data may contain the
terminator byte. Often, binary protocols have fixed message sizes. I suggest to
use MaxInput in that case.