Subject: |
i/o event scan list |
From: |
"F. Gougnaud" <[email protected]> |
Date: |
Wed, 11 May 1994 08:54:56 -0500 |
We developed a driver for the vme i/o module ADAS ICV196 with interrupt service. We are
now interested in how to synchronize the process of ai records with an i/o event on one
bi channel of this module.
We found no way in DCT to attach an ai record to a bi i/o event scan list. The only way
we found to do this was to specify event scan type for the ai records with an event
number related to a specific bi channel, and to call post_event() in the interrupt
service routine.
Could someone propose a better solution ?
Francoise Gougnaud.