Subject: |
Re: pvget to an _output_ record |
From: |
[email protected] (Jeff Hill) |
Date: |
Mon, 5 Dec 94 11:57:32 MST |
>
> It turns out that we have a situation where a pvget directed to
> an ouptput record needs to do some processing (read the actual
> device) rather than simply return the restored value.
>
Perhaps you will want to implement an AI device interface for your
AO device (in addition to the normal AO device interface).
>
> I see that the record structures include entries for things like:
> long rbv; /* Readback Value */
> long orbv; /* Prev Readback Value */
> etc
>
> but it's not clear how these values get set and who uses them. Or even if
> they are applicable to the problem.
>
This is used to restore the database value for AO devices from the
hardware during iocInit.
Jeff
______________________________________________________________________
Jeffrey O. Hill Internet [email protected]
LANL MS H820 Voice 505 665 1831
Los Alamos, NM USA 87545 FAX 505 665 5107
- Navigate by Date:
- Prev:
pvget to an _output_ record Bill Brown
- Next:
Re: pvget to an _output_ record Bob Dalesio
- Index:
<1994>
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
- Navigate by Thread:
- Prev:
pvget to an _output_ record Bill Brown
- Next:
Re: pvget to an _output_ record Bob Dalesio
- Index:
<1994>
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
|