EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: ASYN R4-12
From: Eric Norum <[email protected]>
To: Tech-talk Techtalk <[email protected]>
Date: Thu, 13 Aug 2009 14:27:28 -0500
We are preparing for a release of ASYN. Although the changes are few, they are important. In R4-11 operations that do not use the XXXSyncIO functions fail before iocInit. This means, for example, that calls to asynSetOption() to set serial port parameters fail if done before iocInit(). R4-12 fixes this problem by decoupling autoconnect operations from iocInit(). As well, the asynSerialPort driver now remembers option settings and applies them when the port connects.

We're looking for courageous folks to try the current CVS snapshot and let us know of any problems
		http://www.aps.anl.gov/epics/download/modules/asyn_cvs.tar.gz

=========== Release Notes =============
asynManager: The autoconnect code is now decoupled from EPICS iocInit.

drvAsynSerialPort: Requests to set end-of-string values or serial port parameters are accepted even when the port is not connected. The request takes effect when the port is connected. This makes IOC startup more robust in the face of USB/serial adapters that may be unavailable on startup.

asynInt32Average, asynFloat64Average: If record is processed before new data have arrived (numAverage==0) set record to UDF/INVALID, set UDF to TRUE and leave value unchanged.



--
Eric Norum <[email protected]>
Advanced Photon Source
Argonne National Laboratory
(630) 252-4793



Navigate by Date:
Prev: Re: Keithley 6514 Electrometer support for RS232 Joe Sullivan
Next: RE: CA reconnection problem Jeff Hill
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Keithley 6514 Electrometer support for RS232 Joe Sullivan
Next: TDS3000 Support for edm Mathew Hicks
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·