1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Unexpected Processing Trace (TPRO)
From: haquin <[email protected]>
To: tech-talk <[email protected]>
Date: Tue, 27 Aug 2013 15:50:11 +0200
Hi all,

I have a soft IOC running on Linux PC, connected to a modbus TCP server using Asyn (v4.19) ModbusTCP (v2.4) driver, EPICS R3.14.2.

in my IOC I run the two following records:
record(longin, tstRB) {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynInt32")
  field(INP, "@asyn($(EQPT):Read_All 2)MODBUS_DATA")
  field(TPRO, "1")
}

record(longin, tstRB2) {
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask($(EQPT):Read_All 2 0 0xFFFF )MODBUS_DATA")
  field(TPRO, "1")
}

Both records read the same register in the modbus table which I know is a constant value.

At execution time, I have the following messages for the record tstRB using asynInt32 but no messages related to tstRB2 using asynUInt32Digital:
cbLow: Process tstRB
cbLow: Process tstRB
cbLow: Process tstRB
cbLow: Process tstRB
cbLow: Process tstRB

If I use asynFloat64 iso asynInt32 I also have the messages,
I expected no messages in all cases since the read value is not changing, I didn't expected the behaviour to be DTYP dependent ... Am I wrong ?

Regards
begin:vcard
fn:Christophe Haquin
n:Haquin;Christophe
email;internet:[email protected]
tel;work:02 31 45 46 61
x-mozilla-html:FALSE
version:2.1
end:vcard


Replies:
RE: Unexpected Processing Trace (TPRO) Mark Rivers

Navigate by Date:
Prev: RE: TPG261 : "message too small=0" for EPICS Mark Rivers
Next: CS-Studio Census Eric Berryman
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: TPG261 : "message too small=0" for EPICS Sanguk Won
Next: RE: Unexpected Processing Trace (TPRO) Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 20 Apr 2015 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·