Hello guys,
Thanks for all the responses. I much appreciate your input.
Cheers, Chanaka.
On Oct 3, 2013, at 8:05 AM, Dirk Zimoch wrote:
> On 03.10.2013 07:37, L. C. De Silva wrote:
>> Hi all,
>>
>> I am interested in implementing alarm handler warnings via email and text. Is this supported in EPICS framework? If so, can somebody point me to the relevant information?
>>
>> Thanks, Chanaka.
>>
>>
>
> With StreamDevice, you can send emails. Not from the alarm handler, but from a record. (Handle with care: SCAN=".1 second" may be a bad idea.)
> All you need is access to a (not too suspicious) mail server from your IOC and a little bit of knowledge about the sendmail protocol:
>
> Terminator = CR LF;
> ExtraInput = Ignore;
> ReplyTimeout = 1000;
>
> @mismatch { out "QUIT"; disconnect; }
>
> mail_start {
> connect 10000;
> in "220";
> out "HELO";
> in "250";
> out "MAIL FROM:\$1";
> in "250";
> out "RCPT TO:\$2";
> in "250";
> out "DATA";
> in "354";
> out "From: \$1";
> out "To: \$2";
> out "Subject: Report from \$1";
> out "";
> }
>
> mail_end {
> out ".";
> in "250";
> out "QUIT";
> disconnect;
> }
>
> send {
> mail_start;
> out "Your problem is: %s";
> mail_end;
> }
- References:
- Sending alarm warnings via email and text L. C. De Silva
- Re: Sending alarm warnings via email and text Dirk Zimoch
- Navigate by Date:
- Prev:
Re: Sending alarm warnings via email and text Martin L. Smith
- Next:
lvDCOM (LabVIEW -> EPICS PVs on Windows) freddie.akeroyd
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Sending alarm warnings via email and text Martin L. Smith
- Next:
lvDCOM (LabVIEW -> EPICS PVs on Windows) freddie.akeroyd
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
<2013>
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|