FYI,
I discovered that streamDevice's redirection-to-records feature fails if
the name of the destination PV starts with a number:
https://github.com/paulscherrerinstitute/StreamDevice/issues/20
There have been multiple times in the past where streamDevice support
that used the redirection-to-records feature worked in my development
IOC but didn't work when I deployed it to a beamline. This problem
wasn't discovered then because eliminating redirection from the support
was easier than troubleshooting the redirection failure.
This problem is very likely to occur at the APS. The PV prefix for
development IOCs is often the developer's initials. The beamlines are
numbered and the PV prefix for beamline IOCs usually begins with the
beamline number.
I hope this saves someone else a little frustration.
Kevin
- Replies:
- Re: streamDevice redirection-to-records & PVs that start with a number Dirk Zimoch
- Navigate by Date:
- Prev:
Re: Questions about EPICS_PVA_ADDR_LIST Mark Rivers
- Next:
Re: Questions about EPICS_PVA_ADDR_LIST Michael Davidsaver
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
<2018>
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: Questions about EPICS_PVA_ADDR_LIST Mark Rivers
- Next:
Re: streamDevice redirection-to-records & PVs that start with a number Dirk Zimoch
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
<2018>
2019
2020
2021
2022
2023
2024
|