Hi Andy,
That’s brilliant. I will look into this. Thank you for your help.
Kind regards,
Rebecca Harding (she/her)
Controls Software Engineer
Central Laser Facility
Science and Technology Facilities Council
rebecca.harding at stfc.ac.uk
01235 445129
![ukri-stfc](pnge2ansdNM5_.png)
From: Wilson, Andy (DLSLtd,RAL,LSCI) <andrew.wilson at diamond.ac.uk>
Sent: 01 August 2022 11:07
To: tech-talk at aps.anl.gov; Harding, Rebecca (STFC,RAL,CLF) <rebecca.harding at stfc.ac.uk>
Subject: Re: EPICS Archiver Appliance - Auto-delete Old Data
You could do this by configuring the storage URLs for a PV via policies.py, with the last entry as "blackhole://localhost"; then the ETL will delete the data under the specified
conditions.
Here's a bit of policies.py where for certain PVs we delete the data after 6 months.
if userPolicyOverride == 'some-example-policy':
keep_months = 6
[...]
hold = keep_months + 2
gather = 1
sts_url = 'pb://localhost?name=STS&rootFolder=${ARCHAPPL_SHORT_TERM_FOLDER}&partitionGranularity=PARTITION_15MIN&consolidateOnShutdown=true'
mts_url = 'pb://localhost?name=MTS&rootFolder=${ARCHAPPL_MEDIUM_TERM_FOLDER}&partitionGranularity=PARTITION_DAY&hold=2&gather=1'
lts_url = 'pb://localhost?name=LTS&rootFolder=${ARCHAPPL_LONG_TERM_FOLDER}&partitionGranularity=PARTITION_MONTH&hold=%d&gather=%d' % (hold, gather)
blackhole_url = 'blackhole://localhost'
data_stores = [sts_url, mts_url, lts_url, blackhole_url]
Hello TechTalk,
I am using EPICS Archiver Appliance and I am interested in automatically deleting data that is older than a certain threshold. E.g. only keep the last 2 years of data.
Has anybody already done this? Does anyone have any ideas about a good way to approach this problem?
Kind regards,
Rebecca Harding (she/her)
Controls Software Engineer
Central Laser Facility
Science and Technology Facilities Council
rebecca.harding at stfc.ac.uk
01235 445129
![ukri-stfc](pnge2ansdNM5_.png)
This email and any attachments are intended solely for the use of the named recipients. If you are not the intended recipient you must not use, disclose, copy or distribute this email or any of its attachments and should notify
the sender immediately and delete this email from your system. UK Research and Innovation (UKRI) has taken every reasonable precaution to minimise risk of this email or any attachments containing viruses or malware but the recipient should carry out its own
virus and malware checks before opening the attachments. UKRI does not accept any liability for any losses or damages which the recipient may sustain due to presence of any viruses.
|
- References:
- EPICS Archiver Appliance - Auto-delete Old Data Rebecca Harding - STFC UKRI via Tech-talk
- Re: EPICS Archiver Appliance - Auto-delete Old Data Wilson, Andy (DLSLtd, RAL, LSCI) via Tech-talk
- Navigate by Date:
- Prev:
Re: EPICS Archiver Appliance - Auto-delete Old Data Wilson, Andy (DLSLtd, RAL, LSCI) via Tech-talk
- Next:
Write permission of a record Zhang, Tong via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
<2022>
2023
2024
- Navigate by Thread:
- Prev:
Re: EPICS Archiver Appliance - Auto-delete Old Data Wilson, Andy (DLSLtd, RAL, LSCI) via Tech-talk
- Next:
Write permission of a record Zhang, Tong via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
<2022>
2023
2024
|
ANJ, 14 Sep 2022 |
·
Home
·
News
·
About
·
Base
·
Modules
·
Extensions
·
Distributions
·
Download
·
·
Search
·
EPICS V4
·
IRMIS
·
Talk
·
Bugs
·
Documents
·
Links
·
Licensing
·
|