On 2/17/23 13:02, Mark Rivers via Tech-talk wrote:
Folks,
I have solved the problem, and I can now program the SLC500 through the Moxa.
I enabled data logging on the Moxa and I saw that the received data from the PLC was identical to transmitted data to it. I then found that this was true even when the PLC was off! It was clearly a cable problem, as Mark K. suggested.
I misread the pinout of the RJ45 connector on the Moxa. Interestingly, although EIA-561 specifies the pinout for RS-232 on RJ45, I have yet to find a vendor who actually follows the EIA-561 standard. Moxa and ProSoft use a completely different pinout.
Fun right? I used to keep a printout of this table on my desk @nsls2.
It wasn't exhaustive then, so I'm certain it isn't now.
https://www.conserver.com/consoles/Signals/signals.html
- References:
- Moxa terminal server question Mark Rivers via Tech-talk
- RE: Moxa terminal server question PROBLEM SOLVED Mark Rivers via Tech-talk
- Navigate by Date:
- Prev:
RE: Moxa terminal server question PROBLEM SOLVED Mark Rivers via Tech-talk
- Next:
node-epics-ca: A Channel Access client for Node.js (FFI implementation) Wang, Lin via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
<2023>
2024
- Navigate by Thread:
- Prev:
RE: Moxa terminal server question PROBLEM SOLVED Mark Rivers via Tech-talk
- Next:
Moxa Terminal Server question Koennecke Mark via Tech-talk
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
<2023>
2024
|