1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025 Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
<== Date ==> <== Thread ==>

Subject: Re: Motor driver and lost TCP connection
From: Mark Rivers via Tech-talk <tech-talk at aps.anl.gov>
To: Tech Talk <tech-talk at aps.anl.gov>, Torsten Bögershausen <tboegi at edom.se>
Date: Fri, 24 Jan 2025 14:31:33 +0000
Hi Torsten,

You need to be specific about what you mean by "connection is lost".  Does asyn really think the port is disconnected, i.e. the socket is closed?  Or is it just getting timeouts, but the socket is still connected?  You can use the asynReport command or the asynRecord GUI to tell.

Does the poller ever start working again?

What caused the disconnect, a network interruption or power-cycling the controller?

Mark



From: Tech-talk <tech-talk-bounces at aps.anl.gov> on behalf of Torsten Bögershausen via Tech-talk <tech-talk at aps.anl.gov>
Sent: Friday, January 24, 2025 9:06 AM
To: Tech Talk <tech-talk at aps.anl.gov>
Subject: Motor driver and lost TCP connection
 
Hej Motorist,

Working with a Newport Hexapod I realized that there is
a "mismatch" between asyn and the motorDriver.
When the connection is lost, it seems that
a) asyn starts the autoconnect every 5 seconds.
b) the poller tries to poll every 1 second (or so)
However, the polling fails each time.
Is there a better handling ?
Someone who has written something to stop the poller ?

BR
/Torsten


References:
Motor driver and lost TCP connection Torsten Bögershausen via Tech-talk

Navigate by Date:
Prev: Motor driver and lost TCP connection Torsten Bögershausen via Tech-talk
Next: Re: Archiver Appliance 2.0.5 error 500 Michael Davidsaver via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
Navigate by Thread:
Prev: Motor driver and lost TCP connection Torsten Bögershausen via Tech-talk
Next: Controls position at Sigray Richard Farnsworth via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
ANJ, 27 Jan 2025 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions ·
· Download · Search · IRMIS · Talk · Documents · Links · Licensing ·