Subject: |
Re: Changing SCAN field dynamically |
|
From: |
[email protected] (Marty Kraimer) |
|
Date: |
Tue, 18 Apr 1995 10:38:01 -0500 |
Hi,
> >
> > a) set the HSCN to special type SPC_MOD.
> > b) In the special routine call dbPut to change the SCAN field.
> > Note that changing it yourself will not have the desired effect
> > because it is not removed or placed in the appropriate scan list.
> >
> > Again this seems unnecessary. Just let the user change the SCAN field.
> The requirement is NOT for the user to change the SCAN field but the magRec
> to change its SCAN field because this needs to happen automatically and
> it knows when to do it.
In this case I suggest the following:
When and only when it is time to change the scan choice call dbPut to
change the SCAN field.
Marty Kraimer