I am trying to set up a simulation system and have found that there is
an apparent problem with the SIOL field in an analogue output record.
This is described as an INLINK in the documentation and the
aoRecord.ascii file, but is used as an ouput link in the code.
This has also propagated to Capfast, where the Ao symbol has SIOL as an
input link.
I think the code is right and everything else is wrong. Why has noone
complained before?
The same problem also appears to occur with the bo record, and who
knows how many others.