1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  Index 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020 
<== Date ==> <== Thread ==>

Subject: Re: SNC bug and question
From: Peregrine McGehee <peregrine@lanl.gov>
To: Frank Lenkszus <frl@aps.anl.gov>
Cc: tech-talk@aps.anl.gov
Date: Fri, 09 Jan 1998 09:25:46 -0700
Frank Lenkszus wrote:
>
> The question:
> 
> Is there a way to identify unconnected process variables in a sequence
> program without stepping through every channel using seqChanShow? This
> gets pretty laborious when a state program has lots of pv's (100 - 200).

Unconnected channels:
seqChanShow "myseq", "-"

Connected channels:
seqChanShow "myseq", "+"
> 
> Frank

-- 
Peregrine M. McGehee			LEDA Project Engineer
peregrine@lanl.gov			(505) 667-3273
LANSCE-8 Controls and Automation	Los Alamos National Laboratory

References:
SNC bug and question Frank Lenkszus

Navigate by Date:
Prev: Bookmark to EPICS software distribution Bakul Banerjee
Next: Re: SNC bug and question Rozelle Wright
Index: 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020 
Navigate by Thread:
Prev: SNC bug and question Frank Lenkszus
Next: Re: SNC bug and question Rozelle Wright
Index: 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·