Brian McAllister wrote:
>
> > For numeric records (ai, ao, longin, etc) fields ADEL and MDEL are provided.
> > These are alarm and monitor "deadbands". Values must change by specified amounts
> > before monitors are issued. If these are set to a negative value then monitors
> > are posted everytime the record is processed.
>
> What if ADEL and MDEL are 0 ?
>
> ----
> Brian McAllister
Then only on change, i.e. test is for > rather than >=. There is an interesting
history on which it should be.