|
|
Experimental Physics and
| ||||||||||||||||
|
|
Hello! I've been using the VME8-8 instead of the OMS 58 but I use this feature for boosting the drive current to the motors. I'm using version 4.41 of the motor record and there is one gotcha as far as I know .... see below. Note that the pre-move command has a space as part of the command. I found that this was required to get the pre-move to work properly. So, you should check that your signals work with your database. record(motor,"Moto1r") {
field(DESC,"US motor")
field(DTYP,"OMS VME8/44")
field(PREM," AF1")
field(POST,"AN1")
}Marty Smith Argonne National Lab. APS - Controls Group
| ||||||||||||||||
| ANJ, 10 Aug 2010 |
·
Home
·
News
·
About
·
Talk
·
Base
·
Modules
·
Extensions
·
· Distributions · Download · Documents · Links · Licensing · |