Experimental Physics and
| |||||||||||||||||
|
in 3.14 - you database allows you to have 60 character names channel access allows you to search for much longer names but...... you cannot change the fields within the database that may refer to names that are longer than 40 characters as the channel access type dbr_string is configured to be 40 characters. This means that you can define the database to link any of these 60 character named records together - but you cannot change them over channel access during operation. The caution for channel access clients must also be heeded. It is unclear that all of the clients have been tested with the longer names. Bob Bob Dalesio [email protected] 410 557 0297 Maryland 505 667 3414 Los Alamos 505 699 1632 Cell Phone 505 667 6087 Our Secretary (Lisa Marie)
| ||||||||||||||||