On Friday 01 April 2005 01:18, Geoff Savage wrote:
> I'm trying to delay the output of a calcout record using EPICS 3.14.6,
> vxworks 5.5.1. When I set the ODLY field to 1.0 there does not appear
> to be any delay. When I set the ODLY field to 10.0 I get this message
> on the console - "callbackRequest called with invalid priority". Would
> someone please be kind enough to send me an example?
Hi Geoff,
this sounds very much like your calcout record's header and dbd files don't
match. Maybe you are using record support from a different release than your
dbd is from? Some string fields of the calcout record have changed their
sizes somewhere between R3.14.2 and R3.14.6.
Ben