Hi David,
Use 2 bo records. One for the user to write to and a second that writes to the
hardware. The second one monitors the first one with a CP DOL link.
Dirk
David Dudley wrote:
Is there a way for me to set a bo (or ao) record so that it only
processes when it's value is changed?
I've got a number of those records that I only need written to the PLC
when the value is changed.
David
------------------------------------------------------------------------