Hi,
At Diamond we're using the Epics alarm handler. Typically we run a separate alarm handler per subsystem (or beamline). If a PV goes into alarm state we use it to run a script that sends an e-mail to a list of people (the script reads a file that contains a list of e-mail addresses).
We normally run it on a headless server, but the alarm handler program wasn't designed for that (it requires X libraries etc.) So we run through Xvfb (X virtual frame buffer). I think someone on tech-talk suggested that.
I view this as an interim solution until we can upgrade our alarm handling system to something much more configurable and flexible. A few sites have developed systems with nice viewers and database back-ends.
We also have a prototype SMS notification system. This is being developed into something more powerful. But at the moment it's just a script run by the alarm handler, which writes a file into a NFS shared directory, which is picked up by our SMS server software (we use smstools). And connected to the server is a GSM modem (RS232 connection).
http://smstools3.kekekasvi.com/
At the moment, if a user needs a new PV monitored, it requires the controls engineers to reconfigure the alarm handler. So there is nothing in the way of user configuration.
Cheers,
Matthew
> -----Original Message-----
> From: [email protected] [mailto:tech-talk-
> [email protected]] On Behalf Of [email protected]
> Sent: 08 April 2011 01:54
> To: [email protected]
> Subject: alarm auto dialer
>
> Hi,
>
> I was wondering what people are using for automatic alarm notification
> by
> way of phone, email, etc. Is there anything available that would allow
> recipients to configure when and what alarms they want to receive?
>
> Thank you,
> Patrick
--
This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail.
Any opinions expressed within this e-mail are those of the individual and not necessarily of Diamond Light Source Ltd.
Diamond Light Source Ltd. cannot guarantee that this e-mail or any attachments are free from viruses and we cannot accept liability for any damage which you may sustain as a result of software viruses which may be transmitted in or with the message.
Diamond Light Source Limited (company no. 4375679). Registered in England and Wales with its registered office at Diamond House, Harwell Science and Innovation Campus, Didcot, Oxfordshire, OX11 0DE, United Kingdom
- References:
- alarm auto dialer pthomas
- Navigate by Date:
- Prev:
Re: alarm auto dialer Maren Purves
- Next:
Re: alarm auto dialer Greg Tchilinguirian
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: alarm auto dialer Maren Purves
- Next:
Re: alarm auto dialer Greg Tchilinguirian
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|