I think I must have missed the original message that this is a follow-up
to.
But if you use autosave to save the motor's DVAL and OFF, then on reboot
the RBV will be set to the correct value.
Mark
-----Original Message-----
From: [email protected]
[mailto:[email protected]] On Behalf Of [email protected]
Sent: Friday, April 08, 2011 11:26 AM
To: [email protected]
Subject: motor record RBV
The motors that are an issue have no encoders or limit switches, so
nothing for me to reference. Does anyone have a slick solution for
"restoring" a motor's RBV? Perhaps, something like setting the offset
to
the last RBV after a reboot or crash.
Thanks for your time.